Zone Controllers
TAC Xenta 121-FC
Programmable Fan Coil Controller
TAC Xenta 121-FC is an easily programmable controller intended for both
2-pipe and 4-pipe applications, with or without re-heat. It can be configured
for use with a multitude of valve actuator types, such as on/off, multistage,
increase/decrease, PWM, etc. The controller has different types of fan control
and advanced fan control functions, including on/off delays, boosting and
conditioning.
The sequences for cooling, heating and fan are completely user program-
mable, allowing for numerous different applications. For energy savings the
controller has built-in economizer functionality. Use TAC Xenta 121-FC with
any TAC STR room unit.
Set-up is done using the programming tool TAC ZBuilder, which can be run
stand-alone or as a device plug-in to either TAC Vista or LNS. The configura-
tion settings are downloaded into a TAC Xenta 120, prepared with the neces-
sary basic application software.
The controller is a L
o n Ma r k
®
compliant device aimed at communicating on a
LonTalk
®
TP/FT-10 channel. It is able to operate both as a stand-alone device
and as part of a system. Input and output network variables can be monitored
via the TAC Xenta OP, but programming relies on the use of the TAC ZBuilder.
FUNCTIONAL FEATURES
The controller is designed for
both 2 and 4 pipe installations
Multi-functional Heating and
Cooling: heating, cooling and
secondary heating
Multi-stage Fan Control:
up to three stages or analog
speed control
Indoor Air Quality Control:
full support for CO
2
and RH
(Relative Humidity) functions
Exception modes take care of
abnormal conditions like fire
or risk of frost
Configurable In- and Outputs:
all inputs and outputs are con-
figurable to minimize installa-
tion cost
SPECIFICATIONS
Operating voltage
FC/24 . . . . . . . . . . . . . . . . . . . 24 V AC ±20%, 5060 Hz
FC/230 . . . . . . . . . . . . . . . . . . 230 V AC ±10%, 5060 Hz
Power consumption . . . . . . . . . 5 VA
Dimensions . . . . . . . . . . . . . . . 126x122x50mm(5”x4.8”x2”)
Ambient temperature
Operation . . . . . . . . . . . . . . . . 0°C to +50°C (32°F to 122°F)
Storage . . . . . . . . . . . . . . . . . . –20°C to +5C (F to 122°F)
Humidity . . . . . . . . . . . . . . . . . max. 90% RH non-condensing
Enclosure rating . . . . . . . . . . . . IP 30
Digital inputs . . . . . . . . . . . . . . 3, (X1-X3) NO/NC
Thermistor inputs . . . . . . . . . . . 2, (B1-B2) NTC 1.8 kohm at 25°C (77°F)
Universal input . . . . . . . . . . . . . 1, (U1), configurable as thermistor, digital
or analog input
Potentiometer input . . . . . . . . . 1, (R1) 10 kohm
Triac outputs . . . . . . . . . . . . . . 4, (V1-V4) 24 V AC Intern. supplied
Relay outputs . . . . . . . . . . . . . . 3, (K1-K3) 250 V AC, 3A
Relay output . . . . . . . . . . . . . . 1 (K4) FC24 24 V AC, FC230 250VAC, 3A
Voltage output . . . . . . . . . . . . . 1 (Y1) 0-10 V DC
DESCRIPTION
0-073-0621-0 Contr Zone TAC Xenta 121-FC/24
0-073-0622-0 Contr Zone TAC Xenta 121-FC/230
0-073-0914-0 LNS Plug-in