Network Infrastructure
Termination
Terminating resistor for FTT-10 and TP/XF-1250 network segments.
DESCRIPTION
0-073-0905-1 Termination FTT-10
9-073-0020-0 Termination TP/XF-1250
TAC Xenta 913
L
o n Wo r k s
®
/INET Gateway
The TAC Xenta 913 is a cost-effective way to integrate a large variety of
products into a TAC network. The TAC Xenta 913 supports the most com-
monly used open protocols, such as MODBUS, BACnet and L
o n Wo r k s
®
. It
also supports some manufacturer-specific protocols, like I/NET and Clipsal
C-bus.
The TAC Xenta 913 acts as a gateway, and transfers data point values from
one network to another. Configuration is carried out using the TAC XBuilder
programming tool.
Protocol Description/
Model
Driver Description
BACnet BACnet IP /
MS-TP / PTP
BACnet is a standard protocol for building
automation developed by ASHRAE.
Supports BACnet ReadProperty and
WriteProperty messages.
Max. no. of devices: IP: 10, MS-TP: 30, PTP: 10
MODBUS/
J-Bus
MODBUS
Master / Slave
/ TCP
Commonly used protocol by many PLCs and
other equipment manufacturers.
Uses Poll-on-demand to extract data
RTU or ASCII Formats
Supports 01, 02, 03, 04, 05, 06 and 10
MODBUS functions
Max. no. of devices: As Master: 31 Slaves, As
Slave: 1 Master, TCP: 100
M-Bus Metering Bus M-Bus is a standard protocol for meters.
Requires a hardware converteer between RS-232
and M-Bus such as Level-Converter PW20 from
Relay GmbH.
Max. no. of devices: 200
C-Bus Clipsal bus C-Bus is a proprietary communication protocol of
Clipsal Lighting Control Systems.
Max. no. of devices: 50
L
o n Wo r k s
®
FT-10 Lo n Wo r k s
®
is a standard communication,
extensively used in building automation. Up to
400 SNVTs or TAC Xenta network variables.
I/NET Host LAN /
Controller LAN
I/NET is a proprietary protocol for I/NET systems
from TAC.
FUNCTIONAL FEATURES
Bridges the gap between
protocols
The key to seamless integration
of different vendors’ systems
Direct communication with
third party products at the field
level
Migration and update of
systems without replacement of
older equipment