218 Parameter listing and descriptions
ACH550-01 User's Manual
2016 MIN TORQUE 2 -600.0…0%
Sets the second minimum limit for torque (%). Value is a percentage of
the motor nominal torque.
2017 MAX TORQUE 1 0…600.0%
Sets the first maximum limit for torque (%). Value is a percentage of the
motor nominal torque.
2018 MAX TORQUE 2 0…600.0%
Sets the second maximum limit for torque (%). Value is a percentage of
the motor nominal torque.
Code Description Range