ABB RDNA-01 User Manual Page 147

  • Download
  • Add to my manuals
  • Print
  • Page
    / 320
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 146
ACS550-01/U1 User’s Manual 147
Parameters
3023 WIRING FAULT
Defines the drive response to cross wiring faults and to ground faults detected when the drive is NOT running. When
the drive is not running it monitors for:
Improper connections of input power to the drive output (the drive can display fault 35,
OUTPUT WIRING if improper
connections are detected).
Ground faults (the drive can display fault 16, EARTH FAULT if a ground fault is detected). Also, see parameter 3017
EARTH FAULT.
0 =
DISABLE – No drive response to either of the above monitoring results.
Note: Disabling wiring fault (ground fault) may void the warranty.
1 = ENABLE – The drive displays faults when this monitoring detects problems.
3024 CB TEMP FAULT
Defines the drive response to control board overheating. Not for drives with an OMIO control board.
0 =
DISABLE – No response.
1 =
ENABLE – Displays fault 37 (CB OVERTEMP) and the drive coasts to stop.
Code Description
Page view 146
1 2 ... 142 143 144 145 146 147 148 149 150 151 152 ... 319 320

Comments to this Manuals

No comments