ABB RDNA-01 User Manual Page 210

  • Download
  • Add to my manuals
  • Print
  • Page
    / 320
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 209
210 ACS550-01/U1 User’s Manual
Embedded fieldbus
Fault 28 – Serial 1 Err
If the drive’s control panel shows fault code 28,
SERIAL 1 ERR, check for either of the
following:
The master system is down. To correct, resolve problem with master system.
The communication connection is bad. To correct, check communication
connection at the drive.
The time-out selection for the drive is too short for the given installation. The
master is not polling the drive within the specified time-out delay. To correct,
increase the time set by parameter 3019
COMM FAULT TIME.
Faults 31…33 – EFB1…EFB3
The three EFB fault codes listed for the drive in chapter Diagnostics on page 253
(fault codes 31…33) are not used.
Intermittent off-line occurrences
The problems described above are the most common problems encountered with
ACS550 serial communication. Intermittent problems might also be caused by:
marginally loose connections
wear on wires caused by equipment vibrations
insufficient grounding and shielding on both the devices and on the
communication cables.
Page view 209
1 2 ... 205 206 207 208 209 210 211 212 213 214 215 ... 319 320

Comments to this Manuals

No comments