134 Serial communications
ACH550-01 User's Manual
System overview
The drive can be connected to an external control system,
usually a fieldbus controller, either:
• via the standard RS485 interface at terminals X1:28…32 on
the control board of the drive. The standard RS485 interface
provides the following embedded fieldbus (EFB) protocols:
- Modbus
- Metasys® N2
- APOGEE FLN
- BACnet MS/TP.
For more information, refer to manuals Embedded Fieldbus
(EFB) Control (3AFE68320658 [English]), BACnet® Protocol
(3AUA0000004591 [English])
- BACnet/IP
- BACnet/Ethernet.
For BACnet/IP and BACnet/Ethernet there is a separate
RBIP-01 BACnet/IP Router Module. For more information,
refer to manuals RBIP-01 BACnet/IP Router Module
Installation Manual (3AUA0000040168 [English]) and RBIP-
01 BACnet/IP Router Module User’s Manual
(3AUA0000040159 [English])
or
• via a plug-in fieldbus adapter (EXT FBA) module mounted in
expansion slot 2 of the drive. EXT FBAs must be ordered
separately. EXT FBAs include:
-L
ONWORKS®
- Ethernet (Modbus/TCP, EtherNet/IP™, POWERLINK,
PROFINET IO)
- PROFIBUS DP
- CANopen
- CC-Link
- DeviceNet™
- ControlNet™
For more information, refer to the appropriate adapter
module documentation.
Both the embedded fieldbus (EFB) protocol and the plug-in
fieldbus adapter (EXT FBA) module are activated with
parameter 9802 COMM PROT SEL.