Output group 2 can have disconnection delay by connecting inputs 0.5s and 1.0s being connected to +24 V. The system is
binary, which means that the time values of the inputs are added together to give the total delay time.
1.0s0.5s
+24 V
No delay
1.0s0.5s
+24 V
0.5 s delay
1.0s0.5s
+24 V
1.0 s delay
1.0s0.5s+24 V
1.5 s delay
Automatic resetManual monitored reset
For manual resetting, a push button
must be connected between X1 (Reset
1) or X11 (Reset 2) and +24 V. The mon-
itoring contactors for external devices
are to be connected in series with the
push button. For manual reset, X4 (for
Reset 1) and X14 (for Reset 2) serve as
output for resetting the indicator lamps.
For automatic reset, X1 and X4 (Auto
reset 1) or X11 and X14 (Auto reset 2)
must be connected to +24 V. Monitoring
contacts for external devices must be
connected between +24 V and X1 (Auto
reset 1) or X11 (Auto reset 2) . If moni-
toring contacts are not used, X1 and
X11 must be connected to +24 V.
X4X1+24 V
0 V
X11 X14
X4X1
+24 V
X11 X14
There are two separate reset functions;
Reset 1 and Reset 2. The function of
these is dependent on the operating
mode selected (see Selection of oper-
ating mode). Reset 1 and Reset 2 can
be congured for manual or automatic
reset independently of each other by
means of the input's Auto reset 1 and
Auto reset 2.
Q1
Q11
1L
11L
-24 V
Q2
Q12
+24 V
Q13
The safe relay outputs that are dupli-
cated in series break between 1L-Q1
(output group 1) and 11L-Q11 (output
group 2). The loads that break
should be tted with spark arresters
to protect the outputs. The correct
selection of VDR circuit, RC circuit
or diode is appropriate. Note that
the diode extends the disconnection
time of the load.
The safe transistor outputs Q2 (out-
put group 1) and Q12 (output group
2) have an output voltage of -24 V.
Connection of safe transistor
output (-24 V)
Connection of safe relay output
The non-safe transistor output Q13
is high (+24 V) when the outputs
from output group 2 are active. The
function is therefore dependent on
the operating mode selected (see
Selection of operating mode).
Depending on the input function and
the number of sensors connected to
the safety circuit (odd or even number),
the dynamic signal is connected
between different terminals;
Input function 2:
R2T1 R1
T11 R12R11
A dynamic signal is transmitted from T1,
and depending on the number of sensors
in the safety circuit, the signal connects
back to R1 (odd number of sensors) or
R2 (even number of sensors).
A dynamic signal is transmitted from T11,
and depending on the number of sensors
in the safety circuit, the signal connects
back to R11 (odd number of sensors) or
R12 (even number of sensors).
Input function 1:
Connection of Protection/Sensors - Vital 2
Connection of Outputs - Vital 2
Connection of Reset - Vital 2
Time Delay - Vital 2
Connection of information
output